Hitachi Dc Inverter Ac 1.5 Ton User Manual

Get extra 17% discount on Hitachi 1.5 Ton 5 star Inverter Split ac ( Copper Coil, RSB518HBEA.Shop online Hitachi 1.5 Ton 5 star Inverter Split ac ( Copper Coil, RSB518HBEA at low prices on Paytm Mall.

Hitachi Air

Enjoy great offers on AC servicing & repair

To avail the benefits* please call +91-797141-4848, +91-756788-4848 or e-mail us at customercare@jci-hitachi.com.

Expertise that Delivers.

Your dreams need the right support. Hitachi- true business partner, true Air Expert.

Always near you.

Perfection and expertise whenever and wherever you need.

Engineering Excellence Centre

A place where Hitachi creates expert engineers in HVAC, in order to provide world class customer experience.

Scroll down

Conditioning air at home

Home is the only place in our lives where we have total control of our comfort. Let’s make the most of it.

Conditioning air in your business

A business needs the right conditions to flourish. We can help you create the perfect environment.

How can we help you?

If you need product or project advice, technical support, or have any other questions, we're here to help.

April 24, 2019

Hitachi Inverter-driven, Multi-split System, Heat Pump Air Conditioners;

CodeProtection control
P01Pressure ratio protection control
P02High pressure increase protection
P03Inverter current protection
P04Inverter fin temperature increase protection
P05Discharge gas temperature increase protection at the upper part of the compressor
P06Low pressure decrease protection
P09High pressure decrease protection
P0ADemand current protection control
P0dLow pressure increase protection
P11Pressure ratio decrease retry
P12Low pressure increase retry
P13High pressure increase retry
P14Constant speed compressor overcurrent retry
P15Discharge gas temperature increase retry / Low pressure decrease retry
P16Discharge gas super-heat decrease retry
P17Inverter anomaly retry
P18Abnormal Inverter voltage retry / Inverter failure retry
P26High pressure decrease retry

Alarm Codes;

Code: 01

Content of Abnormality: Tripping of Protection Device


1.5 Ton Truck

Leading Cause: Failure of Fan Motor, Drain Discharge, PCB, Relay

Code: 02

Content of Abnormality: Tripping of Protection Device

Leading Cause: Activation of PSH

Code: 03

Content of Abnormality: Abnormality between Indoor (or outdoor) and Outdoor (or Indoor)

Leading Cause: Incorrect Wiring. Failure of PCB. Tripping of Fuse. Power Supply OFF.

1.5 Ton Air Conditioner

Code: 04

Content of Abnormality: Abnormality between Inverter and Control PCB

Leading Cause: Failure in Transmission between PCBs

Code: 05

Content of Abnormality: Abnormality of Power Source Wiring

Leading Cause: Reverse Phase Incorrect Wiring

Code: 06

Content of Abnormality: Voltage Drop by Excessively Low or High Voltage to Outdoor Unit

Leading Cause: Voltage Drop of Power Supply, Incorrect Wiring or Insufficient Capacity of Power Supply Wiring

Code: 07

Content of Abnormality: Decrease in Discharge Gas Superheat

Leading Cause: Excessive Refrigerant Charge, Expansion Valve Open Lock

Code: 08

Content of Abnormality: Increase in Discharge Gas Temperature

Leading Cause: Insufficient Refrigerant. Ref. Leakage, Clogging or Expansion Valve Close Lock

Code: 09

Content of Abnormality: Tripping of Protection Device

Leading Cause: Failure of Fan Motor

Code: 11


Content of Abnormality: Inlet Air Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 12

Content of Abnormality: Outlet Air Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 13

Content of Abnormality: Freeze Protection Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 14

Content of Abnormality: Gas Piping Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 19

Content of Abnormality: Failure of Fan Motor

Leading Cause: Failure of Fan Motor

Code: 21

Content of Abnormality: High Pressure Sensor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 22

Content of Abnormality: Outdoor Air Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 23

Content of Abnormality: Discharge Gas Thermistor on Comp

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 24

Content of Abnormality: Evaporating Thermistor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 29

Content of Abnormality: Low Pressure Sensor

Leading Cause: Failure of Thermistor, Sensor, Connection

Code: 30

Content of Abnormality: Incorrect Wiring Connection

Leading Cause: Incorrect Wiring Connection between Outdoor Unit, CH Unit and Indoor Unit

Code: 31

Content of Abnormality: Incorrect Setting of Outdoor and Indoor Unit

Leading Cause: Incorrect Setting of Capacity Code

Code: 32

Content of Abnormality: Abnormal Transmission of Other Indoor Unit

Leading Cause: Failure of Power Supply, PCB in Other Indoor Unit. Failure of Other Indoor Unit of the Same Refrigerant Cycle.

Code: 35

Content of Abnormality: Incorrect Setting in Indoor/Outdoor Unit No.

Leading Cause: Existence of the same Indoor Unit No. in the same refrigerant cycle

Code: 38

Content of Abnormality: Abnormality of Protective Circuit in Outdoor Unit

Leading Cause: Failure of Indoor Unit PCB. Incorrect Wiring Connection to PCB in Outdoor Unit

Code: 39

Content of Abnormality: Abnormality of Running Current at Constant Compressor

Leading Cause: Overcurrent, Melted Fuse of Failure of Current Sensor

Code: 43

Content of Abnormality: Pressure Ratio Decrease Protection Activating

1.5 ton truck

Leading Cause: Failure of Compressor, Inverter

Code: 44

Content of Abnormality: Low Pressure Increase Protection Activating

Leading Cause: Overload to Indoor in Cooling, High Temperature of Outdoor Air in Heating Expansion Valve Open Lock

Hitachi split ac 1.5 ton

Code: 45

Content of Abnormality: High Pressure Increase Protection Activating


Leading Cause: Overload Operation. Excessive Refrigerant Clogging of Heat Exchanger

Code: 46

Content of Abnormality: High Pressure Decrease Protection Activating

Leading Cause: Insufficient Refrigerant

Code: 47

Content of Abnormality: Low Pressure Decrease Protection Activating

Leading Cause: Insufficient Refrigerant. Expansion Valve Close Lock. Refrigerant Leakage

Code: 51

Content of Abnormality: Abnormality of Current Sensor for Inverter

Leading Cause: Failure of Sensor on Inverter PCB

Code: 52

Content of Abnormality: Overcurrent Protection Activating

Leading Cause: Overload, Overcurrent, Locked to Compressor

Code: 53

Content of Abnormality: IPM Protection Activating

Leading Cause: Automatic Stoppage of IPM

Code: 54

Content of Abnormality: Increase in Inverter Fin Temperature

Leading Cause: Abnormal Inverter Fin Thermistor, Abnormal Outdoor Fan

Code: 56

Content of Abnormality: Abnormality of Detection for Fan Motor Position

Leading Cause: Abnormal Detection Circuit of Transmission

Code: 57

Content of Abnormality: Fan Controller Protection Activating

Leading Cause: Abnormal Fan Speed

Code: 58

Content of Abnormality: Abnormality of Fan Controller

Leading Cause: Overcurrent, Abnormal Fan Controller Fin

Code: 59

Content of Abnormality: AC Chopper Circuit Protection

Leading Cause: Failure of FET, Power Supply, CT for Fan Motor

Code: EE

Content of Abnormality: Compressor Protection

Leading Cause: 3 Time Occurrence of Alarm Giving Damage to Compressor within 6 hours

Code: dd

Content of Abnormality: Incorrect Wiring between Indoor Units

Leading Cause: Incorrect Wiring between Indoor Units and Remote Control Switch

Remote Controller-Model: PC-2H2

Code: 01

Cause: Safety Device of the Indoor Unit is tripped (internal Thermostat, *Float Switch)

Code: 02

Cause: Safety Device of the Outdoor Unit is tripped

Code: 03

Cause: Transmission Abnormality between Indoor Unit and Outdoor Unit

Code: 05

Hitachi Dc Inverter Ac 1.5 Ton User Manual Download

Cause: Picking up phase Abnormality

Code: 08

Cause: Abnormality High Temperature on the Top of Compressor

Code: 11

Cause: Thermistor Abnormality for inlet Air Temperature

Code: 12

Cause: Thermistor Abnormality for outlet Air Temperature

Code: 13

Cause: Thermistor Abnormality for Freezing Temperature

Code: 20


Cause: Thermistor Abnormality for Compressor Top Temperature

Code: 22

Cause: Thermistor Abnormality for Outdoor Air Temperature

Code: 24

Cause: Thermistor Abnormality for Outdoor Evaporating Temperature (defrosting)

Code: 25

Cause: Thermistor Abnormality for Condensing Temperature

Code: 32

Cause: Transmision Abnormality between Master and Slave

Code: 38

Cause: Abnormality in the Picking up Circuit protection

Code: 41

Cause: Excessive Overload during Cooling Operation

Code: 42

Cause: Excessive Overload during Heating Operation

Regarding the retry control, the lastest retry code will be indicated unless the protection control related with the frequency control is indicated.

Troubleshooting

This Is Not Abnormal

  • Smells from Indoor Unit; Smell adheres on indoor unit after a long period of time. Clean the air filter and panels or allow a good ventilation.
  • Sound from Deforming Parts; During system starting or stopping, an abrading sound might be heard. However, this is due to thermal deformation of plastic parts. It is not abnormal.
  • Steam from Outdoor Heat Exchanger; During defrosting operation, ice on the outdoor heat exchanger is melted, resulting in making steam.
  • Dew on Air Panel; When the cooling operation continues for a long period of time under high humidity conditions (higher than 27°C DB/80% R.H), dew can form on the air panel.
  • Refrigerant Flow Sound; While the system is being started or stopped, sound from the refrigerant flow may be heard.

Not Cooling Or Heating Well

  • Check for obstruction of air flow of the outside or inside units.
  • Check if too much heat source exists in the room.
  • Check if the air filter is clogged with dust.
  • Check to see if the doors or windows are opened or not.
  • Check if the temperature condition is not within the operation range.

Not Operate

  • Check for electrical wiring.
  • Check for dip switch setting.
  • Check whether the “SET TEMP” is set at the correct temperature.
  • In the case that “RUN” lamp on remote control switch is flickering every 2 seconds, check for connection of remote control line.
  • In the case that “RUN” lamp flashes 5 times (5 seconds) with unit number and alarm code displayed, refer to the next item “18.2 Troubleshooting by Alarm Code” and the “Service Manual”.
  • In the case that no alarm code is indicated and normal operation is not available, refer to the “Service Manual” because abnormality of some device is suspected.